EasyManua.ls Logo

Siemens SIMATIC ET 200pro - 9.2.4 Mounting and wiring the power plug connector

Siemens SIMATIC ET 200pro
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
SIMATIC - ET 200pro motor starter
9-8 GWA 4NEB 950 5661-02 DS 04
9.2.4 Mounting and wiring the power plug connector
Mount and wire the power plug connector according to the following
specifications:
Step Procedure
1 Route the cable through the cable gland, the matching enclosed seal insert
and the plug case.
The seal insert is available in the following grades:
Permitted outer diameter of the cable Seal insert
7.0 to 10.5 mm
9.0 to 13.0 mm
11.5 to 15.5 mm
Green
Red
white
2
Insulate the cable to a length of 20 mm.
3
Insulate the wires to a length of 8 mm.
4 Secure the contact sockets / contact pins to the wires by crimping with a
suitable tool (see Chapter A.2) or solder them.
5 Sort the contact sockets / contact pins in the socket insert / pin insert
according to the assignments as shown in Chapter 9.2.2 and Chapter
9.2.3. The contact sockets / contact pins should not snap into place yet.
Check the correct assignment. Push the contact sockets / contact pins into
the socket insert / pin insert until the snap into place.
Already mounted contact sockets / contact pins can be removed using a
dismounting tool (see Chapter A.2).
6 Ensure the coding is in the right position. Pull the cables back and use the
enclosed Philips screws to firmly screw the socket insert / pin insert into
the plug case.
7 Screw the cable gland down firmly. Make sure that the cable is not twisted
against the plug case.
Table 9-2: Mounting and wiring the power plug connector

Table of Contents