Connecting
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
9-7
9.2.3 Plug connector for motor starter
The power plug connectors X1 for infeed and/or X2 for consumer unit connec-
tion to the motor starters consist of the following components:
Figure 9-6: Plug connector for motor starter
Caution
When inserting the pin insert or socket insert in the plug case, observe the posi-
tion of the coding.
Plug case
Socket insert
Contact sockets
Cable gland
X1 infeed HAN Q4 / 2-socket
with seal insert
Coding
Socket Assignment X1
1 Phase L1
2 Phase L2
3 Phase L3
4 Not used
11 No t us e d
12 Not used
PE (yellow / green)
X2 consumer unit connection HAN Q8/0 pin
Pin Assignment X2
1 Phase L1
2 Not used
3 Phase L3
4 Brake L1
(switched)
5 Temperature
sensor
1)
6 Brake L3 (direct)
7 Phase L2
8 Temperature
sensor
1)
PE (yellow / green)
1) only sDSSte / sDSte and sRSSte / sRSte
43
21
1211
PE
Coding
4
3
2
1
8
7
6
Coding
PE
5
Plug case
Pin insert
Contact pins
Cable gland
with seal insert
Coding