D.3.5 Data record 75 – read logbook – events
The data record can contain 21 entries. When all the places have been written,
the first entry is overwritten.
Note
The newest entry is entered at the end of the data record. The remaining
entries are shifted up by one entry.
354 Sensor supply overload
355 Process image error
365 Incorrect parameter value
ID no. of the incorrect parameter
371 Memory module defective Exact cause additionally in the
logbook – device errors
374 Memory module programming defective
378 FW download defective
381 Error in self-test (=device error) Exact cause additionally in the
logbook – device errors
1406 Cold running tripping
Byte Meaning Value range Increment Note
0…3 Hours of operation –
device
1…4294967295 1 s Oldest
entry
4…5 ID number device error 0…± 32767 signed 16*
= twin complement
1
..
120
123
Hours of operation –
device
1…4294967295 1 s Last,
latest
entry
124
125
ID number device event 0…± 32767 signed 16*
= twin complement
1
* + :Incoming event
– :Outgoing event
Table D-8: Data record 75 – read logbook – events
ID no. Trips – signals Note
Table D-7: Read signals in the logbook – trips (Continued)