Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-23
D.3.9 Data record 94 – read measured values
ID no. Byte Meaning Value range /
[coding]
Increme
nt
Note
Measured values
501 4…5 Remaining cooling time of the
motor
0…1800 s 0.1 s
502
6
0…6
Motor heating 0…200% / [0…100] 2%
6
7
Asymmetry [0]: No asymm.
[1]: Asymm. (≥ 40%)
Tripping limit
depends on
asymmetry
0 = 100%
1 = 75%
503 7 Value asymmetry
1)
0…100% / [0…100] 1% —
504 0 Phase current I
L1 pres (%)
0…796.9% 3.125% 8-bit current for-
mat
505 1 Phase current I
L2 pres(%)
0…796.9% 3.125% 8-bit current for-
mat
506 2 Phase current I
L3 pres(%)
0…796.9% 3.125% 8-bit current for-
mat
507 3 Reserved = 0
8 Reserved = 0
9 Reserved = 0
10 Reserved = 0
11 Reserved = 0
12...13 Reserved = 0
14...15 Reserved = 0
509 20 Reserved = 0
510 22...23 Reserved = 0
511 24...25 Reserved = 0
512 26...27 Reserved = 0
513 28...31 Phase current I
L1(eff)
±0...20 A 0.01 A —
514 32...35 Phase current I
L2(eff)
±0...20 A 0.01 A —
515 36...39 Phase current I
L3(eff)
±0...20 A 0.01 A —
516 40...41 Reserved = 0
517 42 Heat sink temperature is evaluated on starters 1.5 - 12 A to protect the power mod-
ule
518 43 Reserved = 0
Table D-13: Data record 94 – read measured values