10.3.2 Thermal motor model – settings
The following table shows the settings of the device parameters:
10.3.3 Signals and actions, measured values and statistical data
The device function 'Thermal motor model' delivers the following signals, mea-
sured values and statistical data:
Signals and actions
Device parameters Default Adjustment range
Response to overload – thermal motor
model
Trip without restart Trip without restart /
Trip with restart /
Warning
Tripping class 10 5, 10, 15, 20
(only for DSe HF,
RSe HF, sDSSte /
sDSte, sRSSte /
sRSte)
Recovery time 1.5 min. 1 min. ... 30 min.
Idle time 0 0 to 255 seconds
Table 10-3: Device parameters for thermal motor model – settings
Signal Action
Thermal motor model – overload —
Overload tripping Tripping (overload present)
Idle time active —
Cooling time active —