Data formats and data records
SIMATIC - ET 200pro motor starter
D-8 GWA 4NEB 950 5661-02 DS 04
D.3.3 Data record 72 – logbook – device errors
The data record can contain 21 entries. When all the places have been written,
the first entry is overwritten.
Note
The newest entry is entered at the end of the data record. The remaining
entries are shifted up by one entry.
The following device errors can be entered:
Byte Meaning Value range Increment Note
0…3 Hours of operation –
device
1…4294967295 1 s
Oldest
entry
4…5 Object number 0…32767 signed 16 1
...
120…
123
Hours of operation –
device
1…4294967295 1 s Last,
latest
entry
124…
125
Object number 0…32767 signed 16 1
Table D-4: Data record 72 – logbook – device errors
ID no. Device errors – signals Note
400 Reserved No error
401 Reserved (overcurrent detection, hardware) ID no. 331: Line protection
overload
402 — —
403 — —
404 — —
405 — —
406 Reserved (phase loss) ID no. 319: Mains voltage lost
407 Reserved (intermediate circuit voltage too
high)
ID no. 323: intermediate circuit
voltage too high
408 — —
409 Commissioning defective —
410 — —
411 Reserved (overload of the output stage) ID no. 309: Switching element
overload
412 — —
413 — —
414 — —
415 — —
416 — —
Table D-5: Signals in the logbook – device errors