Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-25
D.3.10 Data record 95 – statistical data
ID no. Byte Meaning Value range /
[coding]
Increme
nt
Note
Statistics
607 0 Motor current I
max(%)
0…796.9% 3.125% 8-bit current format
601 1
6
Hours of operation resolu-
tion
0 = 1 minute
1 = 1 second
— Infobit "Hours of
operation resolution"
1
7
Hours of operation –
Select
0 = Motor
1 = Device
— Infobit "Hours of
operation hours of
operation selection"
4…7 Hours of operation –
motor / device
0…4294 967 295 1 s —
603 8…11 Number of motor starts
clockwise
0…4294 967 295 1 —
604 12…15 Number of motor starts
counterclockwise
0…4294 967 295 1 —
605 16…17 Number of motor overload
trippings
0…65535 1 —
606 2…3 Last tripping current 0…1000% 3.125% 9-bit current format
602 28...31 Hours of operation, motor 0…4294 967295 1 s Resolution is signaled
by infobit "hours of
operation resolution"
608 24...27 Last tripping current
I
A (eff)
±0...20 A 0.1 A —
609 20...23 Motor current I
max(eff)
±0...20 A 0.1 A —
610 18...19 Reserved = 0
611 32...35 Hours of operation – motor
current
= 18...49.9% x I
e max
0…4294 967295 1 s Resolution is signaled
by infobit "hours of
operation resolution"
612 36...39 Hours of operation – motor
current
= 50...89.9% x I
e max
0…4294 967 295 1 s
613 40...43 Hours of operation – motor
current
= 90...119.9% x I
e max
0…4294 967 295 1 s
614 44...47 Hours of operation – motor
current
= 120...1000% x I
e max
0…4294 967 295 1 s
615 48...49 Reserved = 0
616 50...51 Number of switching ele-
ment overload trippings
0…65535 1
Table D-14: Data record 95 – statistical data