Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-15
D.3.6 Data record 81 – read base setting DS 131
The structure and content of data record 81 correspond to those of data record
131. Data record 81 delivers the default values for all the parameters of the DS
131.
D.3.7 Data record 92 – read device diagnosis
Ghosted signaling bits are not supported by ET 200pro motor starters.
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Switch / Control:
301 0
0
Ready (Automatic)
Device ready to operate via host (e.g. PLC)
Signaling bit is continuously updated
306 0
1
Motor CLOCKWISE
Switching element 1 switched on
Signaling bit is continuously updated
307 0
2
Motor COUNTER-CLOCK-
WISE
Switching element 2 switched on
Signaling bit is continuously updated
309 0
3
Switching element overload F5,
F24
E.g., power semiconductor too hot and tripping
Signaling bit is deleted when cause of the
trip has been removed and acknowledged
with trip reset
308 0
4
Switching element defective F9 E.g., contactor fused, jammed or power semi-
conductor shorted
Signaling bit can only be deleted by switch-
ing the supply voltage (DC 24 V-NS) off / on
when error cause has been removed
310 0
5
Emergency start active
Signaling bit is deleted when emergency start
is deactivated
302 0
6
Group error
At least 1 error that generates an F no. is set.
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset, autoreset, OFF command
304 0
7
General warning
At least 1 warning is present
Signaling bit is continuously updated
318 1
0
Supply voltage for switching
element missing
F17,
F24
Signaling bit is automatically deleted when
cause of the trip has been removed
319 1
1
Mains voltage lost F17,
F24
Signaling bit is deleted when the cause of the
trip has been removed and acknowledged with
trip reset (occurs even if input or output side of
the primary voltage is missing; valid for soft
starters
311 1
2
Lock-out time active
For reversing starter
Signaling bit is continuously updated
Table D-10: Data record 92 – read device diagnosis