Data formats and data records
SIMATIC - ET 200pro motor starter
D-16 GWA 4NEB 950 5661-02 DS 04
312 1
3
Start-up active
In the case of soft starters
Signaling bit is continuously updated
313 1
4
Coasting down active
315 1
5
Brake output active
Brake output is switched on by user
Signaling bit is continuously updated
316 1
6
Electrical braking active
Brake output is switched on by motor starter
Signaling bit is continuously updated
314 1
7
Creep feed active
Signaling bit is continuously updated
1470 19
1
Ready to start for Motor ON
Device ready to operate, switch-on is possible
1414 19
2
Switching element short-cir-
cuited
E.g. contactor fused
Protective function: Motor / Cable / Short circuit
324 2
0
Temperature sensor overload F 4 Overload detected
Signaling bit is continuously updated
325 2
1
Temperature sensor wire
break
F6 Thermistor circuit interrupted
Signaling bit is continuously updated
326 2
2
Temperature sensor short cir-
cuit
F1 Short circuit in thermistor circuit
Signaling bit is continuously updated
327 2
3
Thermal motor model over-
load
F4 Overload detected
Signaling bit is continuously updated
328 2
4
Overload tripping F24 Overload detected and tripping
Signaling bit is deleted when cause of the
trip has been removed and acknowledged
with trip reset / autoreset
329 2
5
Idle time active
Signaling bit is continuously updated
330 2
6
Cooling time active
Signaling bit is continuously updated
305 2
7
Fail-safe tripping F25 Tripped
331 3
0
Line protection overload F4 Cable between motor starter and motor over-
loaded
Signaling bit is continuously updated
332 3
1
Line protection tripping F24 Cable between motor starter and motor over-
load and tripping
Signaling bit is deleted when cause of the trip
is removed and acknowledged with trip reset
333 3
2
Circuit breaker tripped F1,
F24
Signaling bit is deleted if acknowledged with
"Trip reset" and cause of the trip has been
removed.
320 3
3
Current limitation active
Motor current is limited to parameterized
value. Signaling bit is continuously updated
321 3
4
Target value = actual value
Target frequency speed adjuster = actual fre-
quency. Signaling bit is continuously updated
323 3
5
Intermediate circuit voltage
too high
Speed adjuster
Signaling bit is continuously updated
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Table D-10: Data record 92 – read device diagnosis (Continued)