Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-17
322 3
6
Generator motor run
—
Motor feeds power back to motor starter.
Signaling bit is continuously updated
352 3
7
Input control
2)
—
Motor CLOCKWISE, Motor COUNTER-CLOCK-
WISE control commands via the input actions
Signaling bit is continuously updated
340 4
0
Asymmetry detected
—
Asymmetry has occurred
Signaling bit is continuously updated
341 4
1
Asymmetry tripping F24 Asymmetry has occurred and tripping
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset
334 4
2
I
e
limit value exceeded
2)
F7 Limit value exceeded
Signaling bit is continuously updated
335 4
3
I
e
limit value undershot
2)
F8 Limit value undershot
Signaling bit is continuously updated
336 4
4
I
e
limit value tripping
2)
F24 Signaling bit is deleted if acknowledged with
"Trip reset" and cause of the trip has been
removed.
337 4
5
Residual current detected
—
Residual current detected
Signaling bit is continuously updated
338 4
6
Residual current tripping F24 Residual current detected and tripping
339 4
7
Motor block tripping F24 Tripping, blocking current detected for longer
than permitted blocking time
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset
344 5
0
Input 1
2)
—
States of the free inputs (with make contact):
'1' = active, HIGH level present
'0' = inactive, LOW level present
(with break contact inverted)
Signaling bit is continuously updated
345 5
1
Input 2
2)
—
346 5
2
Input 3
2)
—
347 5
3
Input 4
2)
—
348 5
4
Input tripping
2)
F26,
F24
Tripping has occurred
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset / autoreset
349 5
5
Input
tripping end position
clockwise
2)
F26,
F24
Tripping has occurred
Signaling bit is automatically deleted when
cause of the trip has been removed.
Start to the left (counterclockwise) is possi-
ble.
351 5
6
Input warning
2)
—
Warning present
Signaling bit is continuously updated
350 5
7
Input
tripping end position counter
clockwise
2)
F26,
F24
Tripping has occurred
Signaling bit is automatically deleted when
cause of the trip has been removed. Start to
the right (clockwise) is possible.
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Table D-10: Data record 92 – read device diagnosis (Continued)