Data formats and data records
SIMATIC - ET 200pro motor starter
D-18 GWA 4NEB 950 5661-02 DS 04
342 6
0
Earth fault detected
—
Earth-fault current present
Signaling bit is continuously updated
343 6
1
Earth fault tripping F24 Earth-fault current present and tripping
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with trip
reset
353 6
2
Quick stop active
2)
F26,
F24
Quick stop has occurred and tripping
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with trip
reset
354 6
3
Sensor supply overload
2)
F26,
F24
Sensor supply overload has occurred and tripping
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset
361 6
4
Trip reset is carried out
—
Signaling bit is deleted by update or trip reset
in the ready to operate state
362 6
5
Trip reset not possible
—
Cause of the trip is still present!
Signaling bit is deleted by update (new trip
reset) or trip reset in the ready to operate
state
363 6
6
Maximum pointer deleted
—
Signaling bit is always deleted if acknowl-
edged with 'trip reset'.
317 6
7
Supply voltage for electron-
ics too low
—
Signaling bit is automatically deleted when
cause of the trip has been removed
Communication
303 7
0
Bus fault
—
Response monitoring of DP interface expired
Signaling bit is continuously updated
356 7
1
CPU / Master STOP
—
PLC program is no longer being processed
Signaling bit is continuously updated
357 7
2
22
0
Automatic operating mode
Redundant to bit 7.2
—
Automatic (PLC controls)
Signaling bit is continuously updated
358 7
3
22
1
Manual operating mode –
bus
Redundant to bit 7.3
—
Manual operation via field bus (control device
controls)
Signaling bit is continuously updated
1443 22
2
Manual bus – PC controls
359 7
4
22
3
Manual operating mode –
local
Redundant to bit 7.4
—
Manual operation via local device interface
(control device controls)
Signaling bit is continuously updated
7
5
Reserved = 0
360 7
6
Manual operation connec-
tion abort
—
During manual operation, corresponding com-
munication link has been interrupted
Signaling bit is continuously updated
355 7
7
Process image error F26
F24
Process image of the outputs contains illegal
bit combination
Signaling bit is automatically deleted when
cause of the trip is removed
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Table D-10: Data record 92 – read device diagnosis (Continued)