Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-19
1444 22
4
Manual operation local –
input controls
2)
Manual operating mode – local active,
+ input controls active
1445 22
5
Manual local operation – con-
trol device controls
Not supported
1446 22
6
Manual local operation – PC
controls
Manual operating mode – local active,
+ PC controls active
Parameters
364 8
0
Parameterization active
Signaling bit is continuously updated
365 8
1
Incorrect parameter value F16
(F24)
Signaling bit is always deleted if acknowl-
edged with trip reset or valid parameter
received.
Leads to tripping on start-up
366 8
2
Parameter change illegal in
the ON state
Attempted parameter change with motor run-
ning or device function concerned that caused
tripping.
Signaling bit is always deleted if acknowl-
edged with trip reset or valid parameter
received.
368 8
3
Parameter block CPU / Mas-
ter ON
Signaling bit is continuously updated
Motor starter ignores parameters from the
PLC
384 8
4
No external start-up parame-
ters received
Signaling bit is always deleted on change
from start-up to normal operating mode
8
5
Reserved = 0
371 8
6
Memory module defective F26
(F24)
Signaling bit is always deleted if acknowl-
edged with trip reset.
Leads to tripping on start-up
370 8
7
Memory module not plugged Signaling bit is continuously updated
Device function
379 9
0
Self-test active
Signaling bit is continuously updated
380 9
1
Self-test OK
Signaling bit is continuously updated
381 9
2
Error in self-test F9 Signaling bit can only be deleted by switch-
ing the supply voltage (DC 24 V-NS) off / on
when the error cause has been removed.
369 9
3
Factory setting
restored
Signaling bit is always deleted if acknowl-
edged with 'trip reset'.
372
373
374
9
4…5
Memory module
00 : not used (state after power on)
01 : programming active
10 : programming successful
11 : Programming defective F26,
(F24 only for start-up)
Signaling bit is always deleted when
acknowledged with trip reset.
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Table D-10: Data record 92 – read device diagnosis (Continued)