Data formats and data records
SIMATIC - ET 200pro motor starter
D-20 GWA 4NEB 950 5661-02 DS 04
377
375
376
378
9
6…7
FW update
00 : rejected / state after reset
01 : active
10 : successful
11 : defective (F9)
Signaling bit is always deleted if acknowledged
with 'Trip reset'.
367 10 Incorrect parameter number
ID no. (low byte)
In connection 8
1
and 8
2
, does not specify the
first non-accepted parameter
Signal byte is always deleted when
acknowledged with trip reset.
11 ID no. (high byte)
1405 14
0
Cold running active
3)
1 = function active
1406 14
1
Cold running tripping
3)
A current flow has been detected
Pre-warnings
1419 24
2
Pre-warning limit – temporal
tripping reserve undershot
2)
A general warning is generated
1420 24
3
Pre-warning limit – motor
heating exceeded
2)
A general warning is generated
Maintenance
1457 26
0
Maintenance requirement
2)
A general pre-warning is generated
1458 26
1
Maintenance request
2)
A general warning is generated
1459 26
2
Maintenance alarm
Not supported
1460 27
0
Maintenance timer limit
value_1 exceeded
2)
A general pre-warning is generated
Reset maintenance timer per command
1461 27
1
Maintenance timer limit
value_2 exceeded
2)
A general warning is generated
Reset maintenance timer per command
1) error numbers PROFIBUS-DP
2) not on standard motor starters
3) can only be activated via "command"
ID no. Byte Signaling bit F no.
1)
Meaning / Acknowledgment
Table D-10: Data record 92 – read device diagnosis (Continued)