SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
4-9
4.5.3 Diagnosis disconnecting module 400 V (ASM-400 V)
4.5.4 Diagnosis of motor starters DSe, sDSSte / sDSte, RSe, sRSSte / sRSte
Red Group error SF
LED
Status/Cause/Remedy
SF
1)
Operating status
Red General fault (is set by the IM 154-.) / device error
1) Status of the LED in this form only with activated group diagnosis
Red Group error SF DEVICE Device sta-
tus
Red /
green /
yellow
Red/
green/
yellow
Contactor
status
STATE In1-4 Input
1 to 4
Green
LEDs
Status/Cause/Remedy
SF STATE Device
Device status / operating mode
Control via bus
Off Green Green Motor on; no error
(clockwise or counterclockwise for RSe)
Off Off Green Motor off; No error
Off flickers
green
2)
Green Motor on; input controls
Off flashes yel-
low
)
Green Manual operation connection abort without
switch back to automatic mode
Off flickers
yellow
2)
Green Tripping by input control function
(e.g. quick stop)
Off Off Flashes
red
Firmware update
1) Flashing frequency 0.5 Hz
2) Flickering frequency 8 to 10 Hz
Table 4-4: Status and error displays by LEDs for DSe, sDSSte / sDSte, RSe, sRSSte / sRSte