10.4.2 Device parameters for current limits – settings
The following table shows the settings of the device parameters:
10.4.3 Signals and actions
The device function 'Current limits' delivers the following signals and actions:
Device parameters Default Adjustment range
Response to current limit violation Warning Warning / Tripping
Lower current limit 18.75% 18.75% to 100%
Increment: 3.125 %
Upper current limit 112.5% 50% to 150%
Increment: 3.125 %
Blocking current 800% 50% to 1000%
Increment: 50%
Blocking time 1 second 1 sec. to 5 seconds
Increment: 0.5 sec.
Response to residual current detection Tripping Warning / Tripping
Table 10-6: Device parameters for current limits – settings
Signal Action
I
e
limit value exceeded —
I
e
limit value undershot —
I
e
limit value tripping Tripping (limit value violation present)
Residual current detected —
Residual current tripping Tripping (residual current detection)
Motor block tripping Tripping (blocking protection)
Table 10-7: Current limits – signals and actions