SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
10-13
Principle of blocking protection when powering up
The following diagram illustrates the block protection principle when powering
up, that is, the relationship between the blocking current and blocking time:
Figure 10-4: Principle of blocking protection
Principle of blocking protection after powering up
After powering up, the blocking protection runs in continuous operation as
follows:
The blocking time is reduced independently of the parameterized value to 1 s.
The blocking current is limited to a max. 400%.
With a parameterized blocking current < 400%, the parameter value is valid.
When the blocking protection is activated, the motor starter itself generates a
trip command.
The signals "Motor block tripping" and "General fault" are generated.
The maximum pointer "Number of switching element overload trippings" is
increased by 1.
Blocking time
Motor
current
Blocking
current
I
t
Case 1: Motor continues to run
Blocking
Blocking
Motor continues to run
Removed within blocking time
Blocking time
Motor
current
Blocking
current
I
t
Blocking
Blocking
Motor is switched off
after blocking time has elapsed
Case 2: Motor is switched off