SIMATIC - ET 200pro motor starter
10-16 GWA 4NEB 950 5661-02 DS 04
Response to overload - temperature sensor
You use this parameter to set how the motor starter is to respond in the case of
'Overload – Temperature sensor' and if the temperature sensor monitoring is
activated:
• Trip without restart
• Trip with restart
• Warning
Caution
Recovery means that with a pending switch-on command the motor starter
switched on again autonomously once the defect cause has been removed
(autoreset).
Temperature sensor monitoring
You use this device parameter to set whether the temperature sensor cable is
to be monitored for line breaks and short circuits.
Setting range: Yes / No
Device parameters for temperature sensor – settings
The following table shows the settings of the device parameters:
Device parameters Default Adjustment range
Temperature sensor Disabled Disabled /
Thermoclick /
PTC - Type A
Response to overload – temperature
sensor
Trip without restart Trip without restart /
Trip with restart /
Warning
Temperature sensor monitoring Yes Yes / No
Table 10-8: Device parameters for temperature sensor – settings