SIMATIC - ET 200pro motor starter
7-14 GWA 4NEB 950 5661-02 DS 04
7.6 Parameters and technical data
7.6.1 Parameters
There is a description of the parameters in Chapter 10.
The following table indicates the parameters that can be set for the special
modules.
7.6.2 Technical specifications
Parameters
Action,
value range
Factory setting Applicability
Group diagnosis • Disable
•Enable
Disable Module
Table 7-1: Parameters of the special modules
Special module
Mainte-
nance isolat-
ing module
Safety local
mainte-
nance isolat-
ing module
Disconnect-
ing
module 400
V
Dimensions and weight
Installation measurements (mm):width
height
depth
110
230
190
110
230
170
Weight (g) 1405 1600 2200
Module-specific data
Permitted service position any
Vibrations tested complying with IEC 60068,
Part 2-6
2g
Vibrations tested complying with IEC 60068,
Part 2-27
Half-sine 10 g / 11 ms
Allocation type complying with IEC 947-4-1 2 1
Pollution degree complying with IEC 60664
(IEC 61131)
2
Overvoltage category complying with IEC 60664 II
Type of protection complying with IEC 60529 IP65
Shock protection protected against touching by fingers
Table 7-2: Technical data of the special modules