Data formats and data records
SIMATIC - ET 200pro motor starter
D-4 GWA 4NEB 950 5661-02 DS 04
Error code
The following error code are generated by the motor starter:
Error codes, bytes Error message Cause
High Low
00
H
00
H
No error —
Communication interface
80
H
A0
H
Negative acknowledgment for
'Read data record'
• Data record is write-only
80
H
A1
H
Negative acknowledgment for
'Write data record'
• Data record is read-only
80
H
A2
H
Protocol error • Layer 2 (field bus)
• Device interface
• Incorrect coordination
80
H
A9
H
This function is not supported! • DPV1 service does not sup-
port 'read / write data record'
Access to technology
80
H
B0
H
Unknown data record number
(DR no.)
• DR no. in the motor starter
unknown
80
H
B1
H
Incorrect data record length on
writing
• Data record length and speci-
fied data record length are dif-
ferent
80
H
B2
H
Incorrect connector slot number • Connector slot not 1 or 4
80
H
B6
H
Communication partner has
rejected the data transfer!
• Incorrect operating mode
(Automatic, Manual bus, Man-
ual operation local)
• Data record is read-only
• Parameter change illegal in the
ON state
80
H
B8
H
Invalid parameter • Incorrect parameter value
Device resources
80
H
C2
H
Temporary shortage of
resources in the device!
• No free reception buffer
• Data record currently
being updated
• Data record task currently
active at another interface
Table D-1: Error codes