10.7.2 Device parameters for inputs – settings
The following table shows the settings of the device parameters:
Device parameters Default Adjustment range
Input signal extension 0 milliseconds 0 milliseconds to
200 milliseconds
Increment: 10 ms.
Input signal delay 10 milliseconds 10 milliseconds to
80 milliseconds
Increment: 10 ms.
Input 1 – level Make contact break contact / make
contact
Input 2 – level
Input 3 – level
Input 4 – level
Input 1 – action No action No action /
Tripping without
restart /
Tripping with
restart /
Tripping end position
clockwise /
Tripping end position
counterclockwise /
General warning /
Operating mode
'Manual operation
local' /
Emergency start /
Motor CLOCKWISE /
Motor COUNTER-
CLOCKWISE /
Quick stop /
Tr i p re se t
Input 2 – action
Input 3 – action
Input 4 – action
Input 1 – signal not latching latching /
not latching
Input 2 – signal
Input 3 – signal
Input 4 – signal
Table 10-14: Device parameters for inputs – settings