SIMATIC - ET 200pro motor starter
8-10 GWA 4NEB 950 5661-02 DS 04
8.2.7 Parameters
There is a description of the parameters in Chapter 10.
The following table shows which actions or value ranges can be set for each
parameter on the DSe / sDSSte / sDSte and RSe / sRSSte /sRSte motor starters.
Parameters
Action,
value range
Factory setting
Applica-
bility
Rated operating current
•Range1
•Range2
Increment 10 mA
0.15 to 2 A (0.07 to 0.9 kW)
1.5 to 12 A (0.7 to 5.5 kW)
GSD / device
0.15 - 2 A
1.5 - 12 A
Module
Response to 'Supply volt-
age switching element miss-
ing'
Group error
General fault with ON com-
mand
General warning
Group error Module
Load type 3-phase motor
1-phase motor (not for elec-
tronic starters)
3-phase motor Module
Response to overload – ther-
mal motor model
1)
Trip without restart
Trip with restart
Warning
Trip without restart Module
Pre-warning limit value
1)
Motor heating
Time tripping reserve
0% ... 95%
0 s ... 500 s
0%
0s
Module
Recovery time 1.5 min. (for ST)
1 min. ... 30 min. (HF)
Increment 0.5 min.
1.5 min. Module
Protection against voltage
failure
1)
•Yes
•No
Yes Module
Lock-out time for reversing
starter
150 ms fixed
0 s ... 60 s
1)
Tripping class CLASS 10
CLASS 5, 10, 15, 20
1)
CLASS 10 Module
Idle time
Deleting the therm. overload
model when turned on by
control functions at operat-
ing temperature
Increment 1 s
0 to 255 s
0 = deactivated
0 Module
Response to current limit
violation
1)
Warning
•Tripping
Warning Module
Temperature sensor Disabled
•Thermoclick
•PTC Type A.
Disabled Module
Lower current limit value
1)
Increment 3.125%
18.75 to 100%
2)
18.75% Module
Upper current limit value
1)
Increment 3.125%
50 to 150%
2)
112.5% Module
Response to residual current
detection
Warning
•Tripping
Tripping Module
Limit value for current asym-
metry
•30% I
e
30% ... 60% I
e
1)
30% Module
Response to asymmetry Warning
•Tripping
Tripping Module
Table 8-2: Parameters for motor starters DSe, RSe (standard and high feature); sDSSte / sDSte, sRSSte / sRSte