SIMATIC - ET 200pro motor starter
2-4 GWA 4NEB 950 5661-02 DS 04
Order of assembly
You will find an exact description for assembly for:
• Assembling IM 154-. Assembling DP high feature and digital modules in the manual
'Decentralized peripheral system ET 200pro'
• Assembling the rear wall bus module in Chapter 3.4
• Assembling the maintenance isolating module and motor starters in Chapter 3.5
For assembly, proceed as follows:
1. Fit the module holder onto a fixed surface.
2. Start assembling the individual modules on the
module holder from the left.
Observe the following order:
- Interface module IM 154-. DP high feature
- Electronics module 8 DI DC 24 V
- Rear wall bus module for maintenance isolating
module
- Rear wall bus module for DSe direct starter standard
- Terminating module
3. Place the corresponding function modules on the rear wall bus modules and
screw them down.
4. At the interface module IM 154-. DP high feature, set PROFIBUS address 6.
Figure 2-2: Set PROFIBUS address 6
PROFIBUS address 6
OFF ON
64
32
16
8
4
2
1
Coding switch under screw cover
on the front