Data formats and data records
SIMATIC - ET 200pro motor starter
D-12 GWA 4NEB 950 5661-02 DS 04
D.3.4 Data record 73 – read logbook – trips
The data record can contain 21 entries. When all the places have been written,
the first entry is overwritten.
Note
The newest entry is entered at the end of the data record. The remaining
entries are shifted up by one entry.
The following signals can be entered:
Byte Meaning Value range Increment Note
0…3 Hours of operation –
device
1…4294967295 1 s
Oldest
entry
4…5 ID number device error 0…32767 signed 16 1
..
120…
123
Hours of operation –
device
1…4294967295 1 s Last,
latest
entry
124…
125
ID number trip 0…32767 signed 16 1
Table D-6: Data record 73 – read logbook – trips
ID no. Trips – signals Note
309 Switching element overload —
317 Supply voltage for electronics too low —
318 Supply voltage for switching element missing —
319 Mains voltage lost —
323 intermediate circuit voltage too high —
324 Temperature sensor overload —
325 Temperature sensor wire break —
326 Temperature sensor short circuit —
327 Thermal motor model overload —
331 Line protection overload —
334 I
e
limit value exceeded —
335 I
e
limit value undershot —
338 Residual current tripping —
339 Motor block tripping —
341 Asymmetry tripping —
343 Earth fault tripping —
348 Input tripping —
Table D-7: Read signals in the logbook – trips