SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
8-15
Technical data – brake control
(only with order end number ...AA3)
Caution
The brake control and motor control are run through a shared cable. When the
motor is switched off, non-permitted high induction voltages can arise; these
overcouple in the motor cable to the brake control and can thus lead to interfer-
ence in electrical components in the starter.
Brake motors that are controlled via ...AA3 starters should therefore as a gen-
eral principle be equipped with screening units (e.g. RC combinations) for the
main circuit (exception: electronic starters may not be operated with an EMC
protective circuit).
Rated operating voltage AC 400 V
Continuous current
Switch-on current at t < 120 ms
Switch-off current AC 15, at 400 V
eff
0.5 A
5A
0.5 A
Permitted brake (example) with
one-way same direction on
AC400V T <4C 100W
Error message if brake not driven No
Protective measures
Short-circuit protection Yes, 1 A fusible link
Induction protection internal Varistor
External protective circuit
with inductive load
required
Table 8-4: Technical data – brake control