SIMATIC - ET 200pro motor starter
10-28 GWA 4NEB 950 5661-02 DS 04
10.9 Field bus interface
10.9.1 Device parameters
Response to CPU / master STOP
This device parameter configures how the motor starter responds to a CPU /
master STOP:
Retain the last value
Switch substitute value
Caution
This device parameter is only relevant in the operating mode 'Automatic'.
Group diagnosis
You use this parameter to enable or disable diagnosis via PROFIBUS DP (error
type).
General warning diagnosis
Already included as preparation for future I&M (Identification and Maintenance),
but currently no practical effect.
Wait for start-up parameter data records
This bit is set directly by the object manager for DPV1 configuration (project
planning) via STEP 7. It indicates to the motor starter whether a data record
transfer is to follow. Powering up of the motor starter is stopped until comple-
tion of the data record transfer.