Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-29
D.3.12 Data record 100 – read device identification
ID no. Byte Length Value Meaning
Header label
900 0 1 Coordination
0x20 write via C1 channel (PLC)
0x30 write via C2 channel (PC)
0x40 write via device interface (PC)
11Reserved1
21Reserved2
31Reserved3
Device identification (TF)
901 4…11 8 ... Time stamp
1)
902 12…31 20 Siemens AG Manufacturer
903 32…55 24 — MLFB number
904 56 1 0x01 Device family: load feeder
905 57 1 0x01 Device subfamily: Motor starter
906 58 1 0x01 / 0x02 Device class: e.g. direct starter / reversing starter
907 59 1 0x03 System: PROFIBUS DP
908 60 1 0x01 Function group
909 61 1 0x00 Reserved
910 62…77 16 — Short product code
911 78…81 1 ´V... HW output status (byte 0 to byte 3)
912
82 1 0x00 ID number (byte0)
83 1 0x00 ID number (byte1)
84 1 0x80 ID number (byte2)
85 1 0xAF ID number (byte3)
86…87 2 0x00 Reserved
915 88…95 8 ... Service number
96 1 0x00 Reserved
97 1 0x00 Reserved
98 1 0x00 Reserved
99 1 0x00 Reserved
1) Time stamp: Time of factory initialization with factory settings
Table D-16: Data record 100 – read device identification