SIMATIC - ET 200pro motor starter
2-10 GWA 4NEB 950 5661-02 DS 04
Checking the wiring
Check for correct wiring of the ON switch and OFF switch.
6. Press the ON switch
Observe the LEDs
- 8 DI DC 24 V, DI
0
green
- DSe motor starter, STATE green.
- DSe motor starter, DEVICE flashes yellow.
- If SF is red at the DSe motor starter, the parameter for 'Response to resid-
ual current detection' is set to "switch off".
Reset the ON command and switch the voltage 1L+ off briefly to reset the
error.
7. Switch on the supply voltage AC 400 V for the motor starters.
Danger
Make sure that no parts carrying dangerous voltage can be touched.
8. Repeat step 6 and observe the response of the connected consumer unit.
Warning
Make sure that no danger can result from the actuators connected to the motor
starters (e.g. uncontrolled rotary motion of the motor).
9. Press the OFF switch
Observe the LEDs
- 8 DI DC 24 V, DI
1
Off
- DSe motor starter, STATE Off.
- DSe motor starter, DEVICE green