SIMATIC - ET 200pro motor starter
7-16 GWA 4NEB 950 5661-02 DS 04
Switching times at 0.85 ... 1.1 x U
e
• Closing time
• Opening delay
——
425 ... 525 ms
40 ... 60 ms
Insulation resistance
Rated impulse strength U
imp
6 kV
Rated insulation voltage U
i
400 V
Protective separation between main and control
current circuits
400 V, in accordance with EN 60947-1 Appen-
dix N
Circuits with rated voltage U
e
against other circuits
or ground
•0 V< U
e
< 50 V
•300 V < U
e
< 600 V
Testing voltage
complying with IEC 61131, Part 2
DC 500 V
DC 2.6 kV to ground
Special module
Mainte-
nance isolat-
ing module
Safety local
mainte-
nance isolat-
ing module
Disconnect-
ing
module 400
V
Table 7-2: Technical data of the special modules (cont.)