7
05.01
7.1 Line supply fuses, commutating reactors, transformers and main switches
7-210
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
7.1.6 Assigning transformers to the UI modules
Table 7-6 Matching transformers with separate windings for 50 Hz / 60 Hz line supplies
UI module
5 kW
UI module
10 kW
UI module
28 kW
Rated power [kVA] 8.2 15.7 42.6
Pv [W] 600 730 1300
Weight [kg] 60 100 170
Secondary connection
[mm
2
]
4 10 35
Input voltage 3–ph. 500 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 9.95 19 50.7
Primary connection [mm
2
] 4 6 25
Order No.,
6SN1111–0AA02– –1BE0 –1AE0 –1CE0
Input voltage 3–ph. 440 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 11.3 21.6 57.6
Primary connection [mm
2
] 4 6 35
Order No.,
6SN1111–0AA02– –1BF0 –1AF0 –1CF0
Input voltage 3–ph. 415 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 12 22.9 61
Primary connection [mm
2
] 4 6 35
Order No.,
6SN1111–0AA02– –1BG0 –1AG0 –1CG0
Input voltage 3–ph. 400 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 12.4 23.8 63.3
Primary connection [mm
2
] 4 10 35
Order No.,
6SN1111–0AA02– –1BH0 –1AH0 –1CH0
Input voltage 3–ph. 220 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 22.6 43.3 115
Primary connection [mm
2
] 6 25 50
Order No.,
6SN1111–0AA02– –1BC0 –1AC0 –1CC0
Input voltage 3–ph. 200 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated
input current [A]
24.9 47.6 127
Primary connection [mm
2
] 10 25 70
Order No.,
6SN1111–0AA02– –1BJ0 –1AJ0 –1CJ0
7 Line Supply Connection