9.11 Induction motor operation 611A (611D/611U)
9-289
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) 05.01 Edition
9.11 Induction motor operation 611A (611D/611U)
9.11.1 Several induction motors 611A operated in parallel
Several motors can be operated in parallel from an induction motor module.
Several design guidelines must be observed when selecting the motor and mo-
dule.
A maximum drive constellation for parallel operation can include up to eight mo-
tors. Motors connected in parallel to an induction motor module must have the
same V/Hz characteristics. Further, it is recommended that motors should have
the same pole number. If more than two motors are operated from a single mo-
dule, then these motors should have, as far as possible, the same output.
For a twomotor constellation, the power differential between the motors may
not exceed a ratio of 1:10.
The following design guidelines should be observed:
S Selecting the induction motor module rating
Steadystate operation of the motors connected in parallel essentially in
the closedloop controlled range (> n
min
1)
) and preferably in the rated
speed range:
Σ Rated motor currentsv Rated current of the induction motor module
Operation of motors connected in parallel with dynamic loading and in
the openloop controlled range require a higher rating:
1,2 (Σ Rated motor currents) v Rated current of the induction motor
module
The current limit of the induction motor module is increased to 150%
rated current for commissioning.
S The motors should not be loaded above rated torque.
S For highspeed induction motors (e.g. for woodworking), a series reactor
must be connected between the induction motor module and the motor
group:
Rated reactor current: RMS current of the motor group
2)
When taking into account the above information, load and speed steps applied
to individual motors, are corrected. By applying the selection guidelines, a sta-
ble, stallproof operation of the individual motors can be achieved. The speeds
of individual motors are load
dependent. The actually selected speeds can drift apart by several percent due
to the summed slip control.
1) Standard motor: 2pole > 600 RPM
4pole > 300 RPM
6pole > 200 RPM
8pole > 150 RPM
40 V
n
rated
600 RPM
Special motors: n
min
> >
V
rated
motor
Pole pair number
2) Σ Rated motor currents or, when taking into account the load duty cycle, the total RMS currents of the
motor group.