SIMODRIVE 611 Planning Guide (PJU) 05.01 Edition
7.1.7 Assigning main switches
Note
Before poweringdown, terminal 48 of the NE module must be deenergized
10 ms before the contacts of the switch open.
Main switches with leading auxiliary contacts can be used to ensure that
terminal 48 of the NE module is first deenergized.
Recommendation:
Siemens switches, types 3LC.../3KA5... (from the Catalog SIEMENS
Lowvoltage switchgear)
Table 7-7 Assigning the main and auxiliary switches
For UI modules
5 kW 10 kW 28 kW
Switch-
type
3LD21030TK...
+
3LD92203B
3LD25040TK...
+
3LD92503B
3LD27040TK...
+
3LD92803B
For I/R modules
16 kW 36 kW 55 kW 80 kW 120 kW
Switch
type
3LD25040TK...
+
3LD92503B
3LD27040TK...
+
3LD92803B
3LD53301EE00
+
3LD14000A
3LD53301EE00
+
3LD14000A
3LD57301EE00
+
3LD14000A