7.2 Line filter and HF commutating reactors for I/R and UI modules
7-214
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
7.2.1 Assigning the line filters to the I/R modules
Table 7-9 Assigning the line filters to the I/R modules
I/R module
16/21 kW
I/R module
36/47 kW
I/R module
55/71 kW
I/R module
80/104 kW
I/R module
120/156 kW
Filter
components
Line filter 16 kW Line filter 36 kW Line filter 55 kW Line filter 80 kW Line filter 120 kW
Order No.
Line filter
6SN1111–
0AA01–2BA
V
6SN1111–
0AA01–2CA
V
6SN1111–
0AA01–2DA
V
6SN1111–
0AA01–2EA
V
6SN1111–
0AA01–2FA
V
Mounting
position
Wall or floor mounting, refer to dimension drawings, Section 12.
Module width Refer to the dimension drawings, Section 12.
Filter Filter 9 kg 16 kg 19 kg 22 kg 32 kg
I
rated
filter 30 A 67 A 103 A 150 A 225 A
P
v
filter 70 W 90 W 110 W 150 W 190 W
Connection 16/10 mm
2
1)
PE, (M5)
50 mm
2
PE, (M8)
50 mm
2
PE, (M8)
95 mm
2
PE, (M8)
Cable lug acc. to
DIN 46235
Terminals,
Line supply input
LINE
L1, L2, L3, PE
LINE
L1, L2, L3, PE
LINE
L1, L2, L3, PE
LINE
L1, L2, L3, PE
LINE
L1, L2, L3, PE
Terminals,
output
LOAD
L1, L2, L3
LOAD
L1, L2, L3
LOAD
L1, L2, L3
LOAD
L1, L2, L3
LOAD
L1, L2, L3
I
rated
fuse
2)
35 A 80 A 125 A 160 A 250 A
Cooling Non–ventilated Non–ventilated Non–ventilated Non–ventilated Non–ventilated
Radio interfe-
rence suppres-
sion
EN 55011
Cable–borne, limit
value Class A
Cable–borne, limit
value Class A
Cable–borne, limit
value Class A
Cable–borne, limit
value Class A
Cable–borne, limit
value Class A
Table 7-10 Filter packages
Filter packages 16 kW package
6SN1111–
0AA01–2BB0
36 kW package
6SN1111–
0AA01–2CB0
55 kW package
6SN1111–
0AA01–2DB0
80 kW package
6SN1111–
0AA01–2EB0
120 kW package
6SN1111–
0AA01–2FB0
Contents:
6SN1111–0AA00
–
HF commutating
reactor
16 kW
–0BAV
HF commutating
reactor
36 kW
–0CAV
HF commutating
reactor
55 kW
–0DAV
HF commutating
reactor
80 kW
–1EAV
HF commutating
reactor
120 kW
–1FAV
6SN1111–0AA01
–
Line filter 16 kW
–2BAV
Line filter 36 kW
–2CAV
Line filter 55 kW
–2DAV
Line filter 80 kW
–2EAV
Line filter 120 kW
–2FAV
The filter modules can be mounted horizontally and vertically (line at the bottom,
load at the top).
1) The 1st number is valid for cable lugs, the 2nd number is for finely–stranded conductors without connector sleeves.
2) The fuse used must have this rated current. Refer to Table 7-1 for recommended fuses.
Mounting position
of the filter
modules
7 Line Supply Connection