6.3 Technical data
6-173
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
6.3.1 Technical data, line supply infeed modules
Table 6-5 Supply voltage and frequency
S1, S4 = OFF
Vn = 3–ph. 400 V AC
S1 = ON
Vn = 3–ph. 415 V AC
S4 = ON
Vn = 3–ph. 480 V AC
NE modules up to P
n
v 55 kW
I/R modules Pn = 80/120 kW
Power connection: U1, V1, W1
3–ph. 360...440 V AC
3–ph. 300...360 V AC
1)
45...65 Hz
3–ph. 373...457 V AC
3–ph. 312...373 V AC
1)
45...65 Hz
3–ph. 432...509 V AC
3–ph. 408...432 V AC
1)
55...65 Hz
Coil connection: L1, L2
only for 80 kW and 120 kW
2–ph. 360...457 V AC / 45...53 Hz
2–ph. 400...510 V AC / 57...65 Hz
The cabinet wiring, the motor/encoder feeder cables and the DC link connec-
tions should be checked to ensure that there are no ground faults before the
equipment is powered–up for the first time.
t
P
P
max
P
n
P
s6
0.4 P
n
4 min
10 min
t
P
P
max
P
n
P
s6
0.4 P
n
10 s
60 s
t
P
P
max
P
n
0.2 s
10 s
t
P
P
n
4 s
10 s
FP
n
F: F=1.6 applies for all NE modules up to Pn 80 kW
F=1.4 applies for Pn=120 kW
Peak output duty cycle without pre–loading conditionPeak output duty cycle with pre–loading condition
Peak output duty cycle with
pre–loading condition
S6 load duty cycle with
pre–loading condition
Fig. 6-5 Nominal load duty cycles for NE modules
Supply
voltage and
frequency
No ground fault
Nominal load duty
cycles for
NE modules
6 Infeed Modules