7
05.01
7.1 Line supply fuses, commutating reactors, transformers and main switches
7-208
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
7.1.5 Assigning transformers to the I/R modules
Table 7-5 Matching transformers with separate windings for 50 Hz / 60 Hz line supplies
I/R module
16 kW
I/R module
36 kW
I/R module
55 kW
I/R module
80 kW
I/R module
120 kW
Rated power [kVA] 21 47 70 104 155
Pv [W] 750 1380 2100 2800 3700
Weight [kg] 120 160 310 440 540
Secondary connection
[mm
2
]
16 50 70 Cable lug acc. to DIN 46235
Input voltage 3–ph. 500 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 25.2 55.9 84.1 124 183
Primary connection
[mm
2
]
10 35 50 70 Cable lug acc. to
DIN 46235
Order No.,
6SN1111–0AA02– –0BE0 –0CE0 –0DE0 –0EE0 –0FE0
Input voltage 3–ph. 440 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 28.7 63.5 95.5 141 207
Primary connection
[mm
2
]
10 50 50 70 Cable lug, acc.
to DIN 46235
Order No.,
6SN1111–0AA02– –0BF0 –0CF0 –0DF0 –0EF0 –0FF0
Input voltage 3–ph. 415 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 30.4 67.3 101 149 220
Primary connection
[mm
2
]
10 35 50 70 Cable lug, acc.
to DIN 46235
Order No.,
6SN1111–0AA02– –0BG0 –0CG0 –0DG0 –0EG0 –0FG0
Input voltage 3–ph. 400 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 31.5 69.9 105 155 228
Primary connection
[mm
2
]
16 50 70 Cable lug, acc. to DIN 46235
Order No.,
6SN1111–0AA02– –0BH0 –0CH0 –0DH0 –0EH0 –0FH0
Input voltage 3 AC 220 V $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 57.3 127 191 281 415
Primary connection
[mm
2
]
16 50 Cable lug, acc. to DIN 46235
Order No.,
6SN1111–0AA02– –0BC0 –0CC0 –0DC0 –0EC0 –0FC0
Input voltage 3–ph. 200 V AC $ 10 %; 50 Hz – 5 % to 60 Hz + 5 %
Rated input current [A] 63 140 210 309 456
Primary connection
[mm
2
]
35 70 Cable lug, acc. to DIN 46235
Order No.,
6SN1111–0AA02– –0BJ0 –0CJ0 –0DJ0 –0EJ0 –0FJ0
7 Line Supply Connection