7
05.01
7.1 Line supply fuses, commutating reactors, transformers and main switches
7-207
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
Table 7-4 Auto–transformer for 220V input voltage
2)
I/R module
16/21 kW
I/R module
36/47 kW
I/R module
55/71 kW
I/R module
80/104 kW
I/R module
120/156 kW
PD type
1)
3–ph.
220/400 V AC
21 kVA
auto–transformer
46.5 kVA
auto–transformer
70.3 kVA
auto–transformer
104 kVA
auto–transformer
155 kVA
auto–transformer
Order No.,
6SN1111–0AA00–
–0BC0 –0CC0 –0DC0 –0EC0 –0FC0
Pv 412 W 644 W 790 W 1100 W 1340 W
Connection Prim. 16 mm
2
Sec. 16 mm
2
Prim. 70 mm
2
Sec. 50 mm
2
Prim. 95 mm
2
Sec. 70 mm
2
Cable lug acc. to DIN 46235
Fuse, primary 63 A gL 160 A gL 224 A gL 300 A gL 500 A gL
Weight 60 kg 120 kg 135 kg 220 kg 300 kg
Terminal
assignment
1U1 to 1W1=220 V input, 2U1 to 2W1=400 V output, N=neutral point
Max. dimensions
Drilling template in
mm
Top view, footprint
t3
b4
t4
t1
t2
b3
b2
b1
t3
t1
t2
b3
b2
b1
d1
t1 = 370
t2 = 317
t3 = 53
t4 = 10
b1 = 220
b2 = 179
b3 = 41
b4 = 18
Height 330
t1 = 480
t2 = 418
t3 = 62
t4 = 15
b1 = 255
b2 = 205
b3 = 50
b4 = 22
Height 430
t1 = 480
t2 = 418
t3 = 62
t4 = 15
b1 = 300
b2 = 241
b3 = 59
b4 = 22
Height 430
t1 = 530
t2 = 470
t3 = 60
b1 = 325
b2 = 254
b3 = 71
d1 = 12.5
Height 520
t1 = 590
t2 = 530
t3 = 60
b1 = 360
b2 = 279
b3 = 81
d1 = 15
Height 600
7 Line Supply Connection