7
7-203
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
Line Supply Connection
7.1 Line supply fuses, commutating reactors, transformers
and main switches
7.1.1 Assignment of the line supply fuses to the NE modules
Fuses must be used which are designed to protect the line supply feeder
cables.
The following can be used: NH, D, DO with gL characteristics. Without
restricting the performance data of the NE modules, we recommend the
SIEMENS fuse types listed below.
Table 7-1 Assignment of line supply fuses and circuit–breakers to the NE modules
UI module
5/10 kW
UI module
10/25 kW
UI module
28/50 kW
I/R
module
16/21 kW
I/R
module
36/47 kW
I/R
module
55/71 kW
I/R
module
80/104 kW
I/R module
120/156 KW
I
rated
fuse 16 A 25 A 80 A 35 A 80 A 125 A 160 A 250 A
I
fuse
0.2 s
>70 A >100 A >360 A >180 A >360 A >450 A >650 A >865 A
I
fuse
4 s
>50 A >80 A >260 A >130 A >260 A >350 A >505 A >675 A
I
fuse
10 s >42 A >65 A >200 A >100 A >200 A >250 A >360 A >480 A
I
fuse
240 s >30 A >40 A >135 A >60 A >135 A >200 A >280 A >380 A
Recommended SIEMENS fuse types
Rated
voltage
415 VX
16 A D01
Neoz./
B.No.
5SE2116
25 A D02
Neoz./
B.No.
5SE2125
35 A D02
Neoz./
B.No.
5SE2135
Rated
voltage
500 VX
16 A DII
Diazed/
B.No.
5SB261
25 A DII
Diazed/
B.No.
5SB281
80 A DIV
Diazed/
B.No.
5SC211
35 A DIII
Diazed/
B.No.
5SB411
80 A DIV
Diazed/
B.No.
5SC211
Rated
voltage
500 VX
16 A size
00 NH/
B.No.
3NA3805
25 A size
00 NH/
B.No.
3NA3810
80 A size
00 NH/
B.No.
3NA3824
35 A size
00 NH/
B.No.
3NA3814
80 A size
00 NH/
B.No.
3NA3824
125 A size
00 NH/
B.No.
3NA3832
160 A size
1 NH/
B.No.
3NA3136
250 A size 1
NH/B.No.
3NA3144
SIEMENS circuit–breakers
Desig. 3RV1031–
4BA10
3RV1031–
4EA10
3RV1041–
4LA10
3VF3111–
3FQ41–
0AA0
3RV1031–
4FA10
3RV1041–
4LA10
3VF3111–
3FQ41–
0AA0
3VF3211–
3FU41–
0AA0
3VF3211–
3FW41–
0AA0
3VF4211–
3DM41–
0AA0
7