Operation
7.1 Operation
SINAMICS DCP
162 Operating Instructions, 09/2019, A5E34382853K
â‘ 
Memory card available: PDS 0 is copied to the card in parallel
â‘¡
p0802 = 20; p0803 = 0; p0804 = 1
â‘¢
p0802 = 20; p0803 = 0; p0804 = 2
â‘£
For POWER ON, no PDS 0 on the card: PDS 0 is copied from the ROM to the memory card
⑤
At POWER ON, PDS 0 on the card: PDS 0 is copied to the ROM
â‘¥
Memory card
PDS = parameter data set
Figure 7-3 Copying parameter data sets
Using the memory card for series commissioning
The memory card can also be used for series commissioning of several units with the same
parameter assignment.
Procedure:
1. Completely commission a "sample" SINAMICS DCP. As soon as all of the parameters
have been correctly set, carry out "Copy RAM to ROM".
2. Switch off the system and insert a memory card into the CUD. Switch on the system.
3. The parameter assignment is saved on the memory card. If DCC charts are activated in
the system, then these as well as the DCC library are also saved on the memory card.
4. Remove the card (p9400).
5. Insert the card into a CUD that is switched-off and has still not been parameterized.
Switch on the system (POWER ON).