EasyManua.ls Logo

Siemens sinamics dcp - Page 414

Siemens sinamics dcp
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
7.22 Connecting several SINAMICS DCPs in parallel
SINAMICS DCP
412 Operating Instructions, 09/2019, A5E34382853K
For this example, the parallel interface in DCP1 and DCP2 should be deactivated
(p51800 = 0).
As a result of the droop function, as the reactor current setpoint increases, the voltage
controller linearly reduces the internal voltage setpoint to create a softer characteristic.
Parameter p54127 (voltage controller droop) defines the magnitude of this intervention. It
specifies by which factor the internal voltage setpoint must be reduced if the reactor current
setpoint corresponds to the rated current (p55510 = 100 %).
The following diagram shows the principle mode of operation of the droop function.
Figure 7-101 Principle of operation of the voltage controller with droop function
Example:
If, for a 120 kW device (rated current = 200 A, rated voltage = 600 V) parameter p54127 is
set to 5 %, then when a load of 200 A is applied, the voltage decreases by 30 V (= 5 % of
600 V).

Table of Contents

Other manuals for Siemens sinamics dcp

Related product manuals