Electrical connection
5.4 Terminals and connectors
SINAMICS DCP
52 Operating Instructions, 09/2019, A5E34382853K
Terminal block for the 24 V DC power supply and switching contacts
Terminal block X9 with 10 terminals is provided at or in the device (see connection
overviews).
For the 120 kW device, the terminal block for the power supply and switching contacts is
only accessible after first removing the front panel.
Table 5- 1 Terminal arrangement X9
Terminal
Designation
Meaning
Technical specifications
1
P24_EXT
External power supply
24 V DC plus cable
2
M24_EXT
External power supply
24 V DC minus cable
3
VLSE1
NO contact for contactor control
1)
Precharging contactor, side 1
4 VLSE2 NO contact for contactor control
1)
Precharging contactor, side 1
5
HLSE1
NO contact for contactor control
1)
Main contactor, side 1
6
HLSE2
NO contact for contactor control
1)
Main contactor, side 1
7
VLSA1
NO contact for contactor control
1)
Precharging contactor, side 2
8
VLSA2
NO contact for contactor control
1)
Precharging contactor, side 2
9
HLSA1
NO contact for contactor control
1)
Main contactor, side 2
10
HLSA2
NO contact for contactor control
1)
Main contactor, side 2
• Terminal type: Spring-loaded terminal
• Type: PELV 24 V circuit
• Voltage tolerance of the P24 V ext: 18 V to 30 V
• Current consumption:
– for the 30 kW device, In = 5 A
– for the 120 kW device, In = 20 A
• Conductor cross-sections: 1.5 to 2.5 mm²
For the 120 kW device, for connections "P24_EXT" and "M24_EXT", a cross-section of 2.5 mm² must be used.
1)
Contact rating of the "NO contact for the contactor control": 2 A at 30 VAC/DC resistive.
NOTICE
Material damage when the maximum voltage rating of the NO contact for the contactor
control is exceeded
When the maximum voltage rating is exceeded, the NO contact for the contactor control
can be damaged.
• Do not apply a voltage higher than 30 V to the NO contact for the contactor control.