EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - Page 107

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.14 Differential Protection and Its Protected Objects
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
107
Figure 2-35 Add-on Stabilization During Current Transformer Saturation
Identification of DC Components
A further stabilization (restraint) comes into effect when differential secondary currents are simulated by differ-
ent transient behaviour of the current transformer sets. This differential current is caused by different DC time
constants in the secondary circuits during through-current conditions, i.e. the equal primary DC components
are transformed into unequal secondary DC components due to different time constants of the secondary cir-
cuits. This produces a DC component in the differential current which increases the pickup values of the differ-
ential stage for a short period.
Harmonic Stabilization
In transformers in particular, high short-time magnetizing currents may be present during power-up (inrush cur-
rents). These currents enter the protected zone but do not exit it again, so that they produce differential quan-
tities as they seem like single-end fed fault currents. Unwanted differential currents may also be caused by par-
allel connection of transformers or by transformer overexcitation due to excessive voltage.
The inrush current can amount to a multiple of the rated current and is characterized by a considerable 2nd
harmonic content (double rated frequency) which is practically absent during a short-circuit. If the second har-
monic content in the differential current exceeds a selectable threshold, tripping is blocked.
Figure 2-36 Inrush current - Recording Example of the Three Higher-Voltage Currents

Table of Contents

Related product manuals