EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - Page 162

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.19 Impedance Protection (ANSI 21)
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
162
The following relation allows estimation of the rate of change:
Definitions:
X Reactance between the sources of the power swing
f
p
Swing frequency
δ Swing angle
Figure 2-66 shows an example of how the rate of change evolves as a function of the power swing angle. For
an angle of 180° the rate of change is smallest. The further into the power system network (i.e. larger or smaller
angle), the greater the acceleration.
Figure 2-66 Course of the rate of change (f
p
= 1 Hz; X = 10 Ω)
For this reason, the setting value dZ/dt must also be coordinated with the impedance jump occurring at the start
of a short-circuit.
To do so, you determine the minimum operating impedance (ZL, min), form the difference to the setting of the
impedance zone (e.g. Z1) and calculate the impedance gradient, taking into account the one-cycle measuring
interval.
Example
:
U
min
= 0,9 U
N
, I
max
= 1,1 I
N
, u
SC
= 10 %, Δ t = 20 ms
U
N
= 100 V, I
N
= 1 A

Table of Contents

Related product manuals