Introduction
1.3 Characteristics
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
28
Thermal Overload Protection 49
Temperature image of current heat losses (overload protection with full memory capability, single body
thermal model).
Additional adjustable warning levels based on temperature rise and current magnitude.
Consideration of coolant and ambient temperatures possible.
Negative Sequence Protection 46-1, 46-2, 46-TOC
Precise evaluation of negative sequence component of the three phase currents.
Alarm stage when a set unbalanced load is exceeded.
Thermal characteristic with adjustable negative sequence factor and adjustable cooldown time.
High-speed trip stage for large unbalanced loads (can be used for short-circuit protection).
Startup Overcurrent Protection
I> stage for lower speed ranges (e.g. startup of generators with startup converter).
Differential Protection
•Use for generator, motor or transformer differential protection
Tripping characteristic with restraining current;
High sensitivity.
Insensitivity to DC components and current transformer saturation;
High degree of stability even with different degrees of CT saturation.
Restraint feature against high inrush currents with 2nd harmonic;
Restraint feature against transient and steady-state fault currents with 3rd or 5th harmonics;
High-speed tripping in case of high-current faults;
Integrated matching of transformer vector group.
Integrated matching of transformation ratio with consideration of different c.t. rated currents.
Ground Current Differential Protection
Tripping characteristic with restraining current;
Variable selection of measured quantities for all normal system conditions.
High sensitivity.
Additional stabilisation measures against overfunction with external faults.
Underexcitation Protection
Conductance measurement from positive sequence components.
Multi-step characteristic for steady-state and dynamic stability limits.
Consideration of the excitation voltage.