Reverse Power Protection
Calculation of power from positive sequence components.
Highly sensitive and precise active power measurement (detection of small motoring powers even with low
power factor cos ϕ, angle error compensation).
Insensitive to power fluctuations.
Long-time stage and short-time stage (active with closed emergency tripping valve).
Forward Power Supervision
Calculation of power from positive sequence components.
Supervision the active power output for undershooting (P>) or overshooting (P<) the output specified with
individually adjustable power limits.
Optional high-speed or high-accuracy measurement.
Impedance Protection
Overcurrent pickup with undervoltage seal-in (for synchronous machines which take their excitation voltage
from the terminals).
2 impedance zones, 1 overreach zone (switchable via binary input), 4 time stages.
Polygonal tripping characteristics;
Power Swing Blocking (to be activated)
Out-of-step Protection
Based on the well-proven impedance measurement method.
Measurement enabling by positive sequence current component, and measurement blocking by negative
sequence component.
Evaluation of the course of the complex impedance vector;
Optimum matching to power system conditions by selectable slope of the square wave characteristic.
Reliable distinction between power swing centre being in the power system network and in the generator
unit area.
Undervoltage Protection 27
Two-stage undervoltage measurement of positive sequence component of voltages.
Additional stage with settable, voltage-dependent time characteristic.
Overvoltage Protection 59
Two-stage overvoltage measurement of the highest of the three voltages.
Optionally with phase-to-phase voltages or phase-to-earth voltages.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals