Appendix
A.7 Settings
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
584
6002 RE< WARN Rotor E/F 3.0 .. 30.0 kΩ 10.0 kΩ Pickup Value of Warning Stage
Re<
6003 RE<< TRIP Rotor E/F 1.0 .. 5.0 kΩ 2.0 kΩ Pickup Value of Tripping Stage
Re<<
6004 T-WARN-RE< Rotor E/F 0.00 .. 60.00 sec; ∞ 10.00 sec Time Delay of Warning Stage
Re<
6005 T-TRIP-RE<< Rotor E/F 0.00 .. 60.00 sec; ∞ 0.50 sec Time Delay of Tripping Stage
Re<<
6006 X COUPLING Rotor E/F -100 .. 800 Ω 398 Ω Coupling Reactance
6007 R SERIES Rotor E/F 0 .. 999 Ω 50 Ω Series Resistance (e.g. Meas.
Brushes)
6008 I RE< Rotor E/F 1.0 .. 50.0 mA; 0 2.0 mA Pickup Value of Failure Detection
Ire<
6009 PHI I RE Rotor E/F -15.0 .. 15.0 ° 0.0 ° Correction Angle for Ire
6101 REF 1-3Hz REF 1-3Hz OFF
ON
Block relay
OFF Rotor Earth Fault Protection (1-
3Hz)
6102 RE< WARN REF 1-3Hz 5.0 .. 80.0 kΩ 40.0 kΩ Pickup Value of Warning Stage
Re<
6103 RE<< TRIP REF 1-3Hz 1.0 .. 10.0 kΩ 5.0 kΩ Pickup Value of Tripping Stage
Re<<
6104 T-WARN-RE< REF 1-3Hz 0.00 .. 60.00 sec; ∞ 10.00 sec Time Delay of Warning Stage
Re<
6105 T-TRIP-RE<< REF 1-3Hz 0.00 .. 60.00 sec; ∞ 1.00 sec Time Delay of Tripping Stage
Re<<
6106 Qc < REF 1-3Hz 0.00 .. 1.00 mAs 0.02 mAs Pickup Value of open Rotor
Circuit (Qc)
6107A TEST RESISTOR REF 1-3Hz 1.0 .. 10.0 kΩ 3.3 kΩ Testing Resistor
6501 STARTUP MOTOR Start Motor OFF
ON
Block relay
OFF Motor Starting Time Supervision
6502 START. CURRENT Start Motor 5A 0.50 .. 80.00 A 15.60 A Starting Current of Motor
1A 0.10 .. 16.00 A 3.12 A
6503 STARTING TIME Start Motor 1.0 .. 180.0 sec 8.5 sec Starting Time of Motor
6504 LOCK ROTOR TIME Start Motor 0.5 .. 120.0 sec; ∞ 6.0 sec Permissible Locked Rotor Time
6505 I MOTOR START Start Motor 5A 3.00 .. 50.00 A 8.00 A Current Pickup Value of Motor
Starting
1A 0.60 .. 10.00 A 1.60 A
6601 RESTART INHIBIT Restart Motor OFF
ON
Block relay
OFF Restart Inhibit for Motors
6602 IStart/IMOTnom Restart Motor 1.5 .. 10.0 4.9 I Start / I Motor nominal
6603 T START MAX Restart Motor 3.0 .. 320.0 sec 8.5 sec Maximum Permissible Starting
Time
6604 T EQUAL Restart Motor 0.0 .. 320.0 min 1.0 min Temperature Equalization Time
6606 MAX.WARM STARTS Restart Motor 1 .. 4 2 Permissible Number of Warm
Starts
6607 #COLD-#WARM Restart Motor 1 .. 2 1 Number of Cold Starts - Warm
Starts
6608 Kτ at STOP Restart Motor 1.0 .. 100.0 5.0 Extension of Time Constant at
Stop
6609 Kτ at RUNNING Restart Motor 1.0 .. 100.0 2.0 Extension of Time Constant at
Running
6610 T MIN. INHIBIT Restart Motor 0.2 .. 120.0 min 6.0 min Minimum Restart Inhibit Time
7001 BREAKER FAILURE Breaker Failure OFF
ON
Block relay
OFF Breaker Failure Protection
7002 TRIP INTERN Breaker Failure OFF
BO12
CFC
OFF Start with Internal TRIP
Command
7003 CIRC. BR. I> Breaker Failure 5A 0.20 .. 10.00 A 1.00 A Supervision Current Pickup
1A 0.04 .. 2.00 A 0.20 A
7004 TRIP-Timer Breaker Failure 0.06 .. 60.00 sec; ∞ 0.25 sec TRIP-Timer
Addr. Parameter Function C Setting Options Default Setting Comments