Appendix
A.7 Settings
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
585
7101 INADVERT. EN. Inadvert. En. OFF
ON
Block relay
OFF Inadvertent Energisation
7102 I STAGE Inadvert. En. 5A 0.5 .. 100.0 A; 1.5 A I Stage Pickup
1A 0.1 .. 20.0 A; 0.3 A
7103 RELEASE U1< Inadvert. En. 10.0 .. 125.0 V; 0 50.0 V Release Threshold U1<
7104 PICK UP T U1< Inadvert. En. 0.00 .. 60.00 sec; 5.00 sec Pickup Time Delay T U1<
7105 DROP OUT T U1< Inadvert. En. 0.00 .. 60.00 sec; 1.00 sec Drop Out Time Delay T U1<
7201 DC PROTECTION DC Protection OFF
ON
Block relay
OFF DC Voltage/Current Protection
7202 MEAS.METHOD DC Protection mean value
RMS
mean value Measurement Method
(MEAN/RMS Values)
7203 DC >/< DC Protection DC >
DC <
DC > Method of Operation (DC >/<)
7204 U DC >< DC Protection 0.1 .. 8.5 V 2.0 V DC Voltage Pickup
7205 I DC >< DC Protection 0.2 .. 17.0 mA 4.0 mA DC Current Pickup
7206 T DC DC Protection 0.00 .. 60.00 sec; 2.00 sec Time Delay for Trip of DC Protec-
tion
7301 20 mA (B1/1) = Analog Outputs 10.0 .. 1000.0 % 200.0 % 20 mA (B1/1) correspond to
7302 MIN VALUE(B1/1) Analog Outputs 0.0 .. 5.0 mA 1.0 mA Output value (B1/1) valid from
7303 20 mA (B2/1) = Analog Outputs 10.0 .. 1000.0 % 200.0 % 20 mA (B2/1) correspond to
7304 MIN VALUE(B2/1) Analog Outputs 0.0 .. 5.0 mA 1.0 mA Output value (B2/1) valid from
7305 20 mA (D1/1) = Analog Outputs 10.0 .. 1000.0 % 200.0 % 20 mA (D1/1) correspond to
7306 MIN VALUE(D1/1) Analog Outputs 0.0 .. 5.0 mA 1.0 mA Output value (D1/1) valid from
7307 20 mA (D2/1) = Analog Outputs 10.0 .. 1000.0 % 200.0 % 20 mA (D2/1) correspond to
7308 MIN VALUE(D2/1) Analog Outputs 0.0 .. 5.0 mA 1.0 mA Output value (D2/1) valid from
7310 MIN. VALUE B1/2 Analog Outputs -200.00 .. 100.00 % 0.00 % Minimum Percentage Output
Value (B1/2)
7311 MIN.OUTPUT B1/2 Analog Outputs 0 .. 10 mA 4 mA Minimum Current Output Value
(B1/2)
7312 MAX. VALUE B1/2 Analog Outputs 10.00 .. 200.00 % 100.00 % Maximum Percentage Output
Value (B1/2)
7313 MAX.OUTPUT B1/2 Analog Outputs 10 .. 22 mA; 0 20 mA Maximum Current Output Value
(B1/2)
7320 MIN. VALUE B2/2 Analog Outputs -200.00 .. 100.00 % 0.00 % Minimum Percentage Output
Value (B2/2)
7321 MIN.OUTPUT B2/2 Analog Outputs 0 .. 10 mA 4 mA Minimum Current Output Value
(B2/2)
7322 MAX. VALUE B2/2 Analog Outputs 10.00 .. 200.00 % 100.00 % Maximum Percentage Output
Value (B2/2)
7323 MAX.OUTPUT B2/2 Analog Outputs 10 .. 22 mA; 0 20 mA Maximum Current Output Value
(B2/2)
7330 MIN. VALUE D1/2 Analog Outputs -200.00 .. 100.00 % 0.00 % Minimum Percentage Output
Value (D1/2)
7331 MIN.OUTPUT D1/2 Analog Outputs 0 .. 10 mA 4 mA Minimum Current Output Value
(D1/2)
7332 MAX. VALUE D1/2 Analog Outputs 10.00 .. 200.00 % 100.00 % Maximum Percentage Output
Value (D1/2)
7333 MAX.OUTPUT D1/2 Analog Outputs 10 .. 22 mA; 0 20 mA Maximum Current Output Value
(D1/2)
7340 MIN. VALUE D2/2 Analog Outputs -200.00 .. 100.00 % 0.00 % Minimum Percentage Output
Value (D2/2)
7341 MIN.OUTPUT D2/2 Analog Outputs 0 .. 10 mA 4 mA Minimum Current Output Value
(D2/2)
7342 MAX. VALUE D2/2 Analog Outputs 10.00 .. 200.00 % 100.00 % Maximum Percentage Output
Value (D2/2)
7343 MAX.OUTPUT D2/2 Analog Outputs 10 .. 22 mA; 0 20 mA Maximum Current Output Value
(D2/2)
8001 FUSE FAIL MON. Supervision OFF
ON
OFF Fuse Failure Monitor
8101 MEASURE. SUPERV Measurem.Superv OFF
ON
OFF Measurement Supervision
Addr. Parameter Function C Setting Options Default Setting Comments