Appendix
A.7 Settings
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
586
8102 BALANCE U-LIMIT Measurem.Superv 10 .. 100 V 50 V Voltage Threshold for Balance
Monitoring
8103 BAL. FACTOR U Measurem.Superv 0.58 .. 0.90 0.75 Balance Factor for Voltage
Monitor
8104 BAL. I LIMIT S1 Measurem.Superv 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Side 1
1A 0.10 .. 1.00 A 0.50 A
8105 BAL. FACT. I S1 Measurem.Superv 0.10 .. 0.90 0.50 Balance Factor for Current
Monitor S1
8106 BAL. I LIMIT S2 Measurem.Superv 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Side 2
1A 0.10 .. 1.00 A 0.50 A
8107 BAL. FACT. I S2 Measurem.Superv 0.10 .. 0.90 0.50 Balance Factor for Current
Monitor S2
8108 SUM.thres. U Measurem.Superv 10 .. 200 V 10 V Summation Thres. for Volt. Moni-
toring
8109 SUM.Fact. U Measurem.Superv 0.60 .. 0.95 ; 0 0.75 Factor for Volt. Sum. Monitoring
8110 ΣI THRESHOLD S1 Measurem.Superv 5A 0.25 .. 10.00 A 0.50 A Summated Cur. Mon. Threshold
on Side 1
1A 0.05 .. 2.00 A 0.10 A
8111 ΣI FACTOR S1 Measurem.Superv 0.00 .. 0.95 0.10 Summated Current Mon. Factor
on Side 1
8112 ΣI THRESHOLD S2 Measurem.Superv 5A 0.25 .. 10.00 A 0.50 A Summated Cur. Mon. Threshold
on Side 2
1A 0.05 .. 2.00 A 0.10 A
8113 ΣI FACTOR S2 Measurem.Superv 0.00 .. 0.95 0.10 Summated Current Mon. Factor
on Side 2
8201 TRIP Cir. SUP. TripCirc.Superv OFF
ON
OFF TRIP Circuit Supervision
8501 MEAS. VALUE 1> Threshold Disabled
P
Q
Delta P
UL1E
UL2E
UL3E
UE
U0
U1
U2
UE3h
IEE1
IEE2
3I0
I1
I2
PHI
PF
Transducer 1
Disabled Measured Value for Threshold
MV1>
8502 THRESHOLD MV1> Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV1>
8503 MEAS. VALUE 2< Threshold Disabled
P
Q
Delta P
UL1E
UL2E
UL3E
UE
U0
U1
U2
UE3h
IEE1
IEE2
3I0
I1
I2
PHI
PF
Transducer 1
Disabled Measured Value for Threshold
MV2<
8504 THRESHOLD MV2< Threshold -200 .. 200 % 100 % Pickup Value of Measured Value
MV2<
Addr. Parameter Function C Setting Options Default Setting Comments