EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - Page 609

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
609
5671 Differential protection TRIP (Diff
TRIP)
Diff. Prot OUT * * * LED BO 75 71 1 Yes
5672 Differential protection: TRIP L1
(Diff TRIP L1)
Diff. Prot OUT * * * LED BO 75 72 1 Yes
5673 Differential protection: TRIP L2
(Diff TRIP L2)
Diff. Prot OUT * * * LED BO 75 73 1 Yes
5674 Differential protection: TRIP L3
(Diff TRIP L3)
Diff. Prot OUT * * * LED BO 75 74 1 Yes
5681 Diff. prot.: IDIFF> L1 (without
Tdelay) (Diff> L1)
Diff. Prot OUT * on off * LED BO 75 81 2 Yes
5682 Diff. prot.: IDIFF> L2 (without
Tdelay) (Diff> L2)
Diff. Prot OUT * on off * LED BO 75 82 2 Yes
5683 Diff. prot.: IDIFF> L3 (without
Tdelay) (Diff> L3)
Diff. Prot OUT * on off * LED BO 75 83 2 Yes
5684 Diff. prot: IDIFF>> L1 (without
Tdelay) (Diff>> L1)
Diff. Prot OUT * on off * LED BO 75 84 2 Yes
5685 Diff. prot: IDIFF>> L2 (without
Tdelay) (Diff>> L2)
Diff. Prot OUT * on off * LED BO 75 85 2 Yes
5686 Diff. prot: IDIFF>> L3 (without
Tdelay) (Diff>> L3)
Diff. Prot OUT * on off * LED BO 75 86 2 Yes
5691 Differential prot.: TRIP by IDIFF>
(Diff> TRIP)
Diff. Prot OUT * on m LED BO 75 91 2 Yes
5692 Differential prot.: TRIP by
IDIFF>> (Diff>> TRIP)
Diff. Prot OUT * on m LED BO 75 92 2 Yes
5701 Diff. current in phase L1 at trip
(Diff L1:)
Diff. Prot VI * ON
OFF
75 101 4 No
5702 Diff. current in phase L2 at trip
(Diff L2:)
Diff. Prot VI * ON
OFF
75 102 4 No
5703 Diff. current in phase L3 at trip
(Diff L3:)
Diff. Prot VI * ON
OFF
75 103 4 No
5704 Restr. current in phase L1 at trip
(Res L1:)
Diff. Prot VI * ON
OFF
75 104 4 No
5705 Restr. current in phase L2 at trip
(Res L2:)
Diff. Prot VI * ON
OFF
75 105 4 No
5706 Restr. current in phase L3 at trip
(Res L3:)
Diff. Prot VI * ON
OFF
75 106 4 No
5713 Diff. prot: Adaptation factor CT
side 1 (Diff CT-S1:)
Diff. Prot VI ON
OFF
5714 Diff. prot: Adaptation factor CT
side 2 (Diff CT-S2:)
Diff. Prot VI ON
OFF
5742 Diff: DC L1 (Diff DC L1) Diff. Prot OUT * on off * LED BO 75 120 2 Yes
5743 Diff: DC L2 (Diff DC L2) Diff. Prot OUT * on off * LED BO 75 121 2 Yes
5744 Diff: DC L3 (Diff DC L3) Diff. Prot OUT * on off * LED BO 75 122 2 Yes
5745 Diff: Increase of char. phase (DC)
(Diff DC InCha)
Diff. Prot OUT * on off * LED BO 75 123 2 Yes
5803 >BLOCK restricted earth fault
prot. (>BLOCK REF)
REF SP * * * LED BI BO
5811 Restricted earth fault is switched
OFF (REF OFF)
REF OUT on
off
**LEDBO76111Yes
5812 Restricted earth fault is
BLOCKED (REF BLOCKED)
REF OUT on
off
on off * LED BO 76 12 1 Yes
5813 Restricted earth fault is ACTIVE
(REF ACTIVE)
REF OUT on
off
**LEDBO76131Yes
5817 REF protection picked up (REF
picked up)
REF OUT * on off * LED BO 76 17 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation