Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
609
5671 Differential protection TRIP (Diff
TRIP)
Diff. Prot OUT * * * LED BO 75 71 1 Yes
5672 Differential protection: TRIP L1
(Diff TRIP L1)
Diff. Prot OUT * * * LED BO 75 72 1 Yes
5673 Differential protection: TRIP L2
(Diff TRIP L2)
Diff. Prot OUT * * * LED BO 75 73 1 Yes
5674 Differential protection: TRIP L3
(Diff TRIP L3)
Diff. Prot OUT * * * LED BO 75 74 1 Yes
5681 Diff. prot.: IDIFF> L1 (without
Tdelay) (Diff> L1)
Diff. Prot OUT * on off * LED BO 75 81 2 Yes
5682 Diff. prot.: IDIFF> L2 (without
Tdelay) (Diff> L2)
Diff. Prot OUT * on off * LED BO 75 82 2 Yes
5683 Diff. prot.: IDIFF> L3 (without
Tdelay) (Diff> L3)
Diff. Prot OUT * on off * LED BO 75 83 2 Yes
5684 Diff. prot: IDIFF>> L1 (without
Tdelay) (Diff>> L1)
Diff. Prot OUT * on off * LED BO 75 84 2 Yes
5685 Diff. prot: IDIFF>> L2 (without
Tdelay) (Diff>> L2)
Diff. Prot OUT * on off * LED BO 75 85 2 Yes
5686 Diff. prot: IDIFF>> L3 (without
Tdelay) (Diff>> L3)
Diff. Prot OUT * on off * LED BO 75 86 2 Yes
5691 Differential prot.: TRIP by IDIFF>
(Diff> TRIP)
Diff. Prot OUT * on m LED BO 75 91 2 Yes
5692 Differential prot.: TRIP by
IDIFF>> (Diff>> TRIP)
Diff. Prot OUT * on m LED BO 75 92 2 Yes
5701 Diff. current in phase L1 at trip
(Diff L1:)
Diff. Prot VI * ON
OFF
75 101 4 No
5702 Diff. current in phase L2 at trip
(Diff L2:)
Diff. Prot VI * ON
OFF
75 102 4 No
5703 Diff. current in phase L3 at trip
(Diff L3:)
Diff. Prot VI * ON
OFF
75 103 4 No
5704 Restr. current in phase L1 at trip
(Res L1:)
Diff. Prot VI * ON
OFF
75 104 4 No
5705 Restr. current in phase L2 at trip
(Res L2:)
Diff. Prot VI * ON
OFF
75 105 4 No
5706 Restr. current in phase L3 at trip
(Res L3:)
Diff. Prot VI * ON
OFF
75 106 4 No
5713 Diff. prot: Adaptation factor CT
side 1 (Diff CT-S1:)
Diff. Prot VI ON
OFF
5714 Diff. prot: Adaptation factor CT
side 2 (Diff CT-S2:)
Diff. Prot VI ON
OFF
5742 Diff: DC L1 (Diff DC L1) Diff. Prot OUT * on off * LED BO 75 120 2 Yes
5743 Diff: DC L2 (Diff DC L2) Diff. Prot OUT * on off * LED BO 75 121 2 Yes
5744 Diff: DC L3 (Diff DC L3) Diff. Prot OUT * on off * LED BO 75 122 2 Yes
5745 Diff: Increase of char. phase (DC)
(Diff DC InCha)
Diff. Prot OUT * on off * LED BO 75 123 2 Yes
5803 >BLOCK restricted earth fault
prot. (>BLOCK REF)
REF SP * * * LED BI BO
5811 Restricted earth fault is switched
OFF (REF OFF)
REF OUT on
off
**LEDBO76111Yes
5812 Restricted earth fault is
BLOCKED (REF BLOCKED)
REF OUT on
off
on off * LED BO 76 12 1 Yes
5813 Restricted earth fault is ACTIVE
(REF ACTIVE)
REF OUT on
off
**LEDBO76131Yes
5817 REF protection picked up (REF
picked up)
REF OUT * on off * LED BO 76 17 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation