5821 REF protection TRIP (REF TRIP) REF OUT * on * LED BO 76 21 2 Yes
5833 REF adaptation factor CT starpnt.
wind. (REF CTstar:)
REF VI ON
OFF
5836 REF adverse Adaption factor CT
(REF Adap.fact.)
REF OUT on * * LED BO
5837 REF adaptation factor CT side 1
(REF CT-S1:)
REF VI ON
OFF
5838 REF adaptation factor CT side 2
(REF CT-S2:)
REF VI ON
OFF
5840 REF is blocked by phase current
(REF I> blocked)
REF OUT on
off
**LEDBO76401Yes
5841 REF release by U0> (REF U0>
releas.)
REF OUT on
off
**LEDBO76411Yes
5845 REF pickup of I-REF> (I-REF>
pickup)
REF OUT * * * LED BO 76 42 1 Yes
5846 REF characteristic picked up
(REF char.pickup)
REF OUT * * * LED BO 76 43 1 Yes
5847 I0-Diff at REF-Trip (I0-Diff:) REF VI * ON
OFF
76 47 4 No
5848 I0-Restraint at REF-Trip (I0-Res:) REF VI * ON
OFF
76 48 4 No
6503 >BLOCK undervoltage protection
(>BLOCK U/V)
Undervoltage SP * * * LED BI BO
6506 >BLOCK undervoltage protection
U< (>BLOCK U<)
Undervoltage SP on
off
**LEDBIBO7461Yes
6508 >BLOCK undervoltage protection
U<< (>BLOCK U<<)
Undervoltage SP on
off
**LEDBIBO7481Yes
6513 >BLOCK overvoltage protection
(>BLOCK O/V)
Overvoltage SP * * * LED BI BO
6516 >BLOCK overvoltage protection
U> (>BLOCK U>)
Overvoltage SP on
off
**LEDBIBO74201Yes
6517 >BLOCK overvoltage protection
U>> (>BLOCK U>>)
Overvoltage SP on
off
**LEDBIBO74211Yes
6520 >BLOCK inverse undervoltage
protection (>BLOCK Up<)
Inv.Undervolt. SP * * * LED BI BO
6522 Inv. Undervoltage prot. is
switched OFF (Up< OFF)
Inv.Undervolt. OUT on
off
**LEDBO74951Yes
6523 Inv. Undervoltage protection is
BLOCKED (Up< BLOCK)
Inv.Undervolt. OUT on
off
on off * LED BO 74 96 1 Yes
6524 Inv. Undervoltage protection is
ACTIVE (Up< ACTIVE)
Inv.Undervolt. OUT on
off
**LEDBO74971Yes
6525 Inverse Undervoltage Up< picked
up (Up< picked up)
Inv.Undervolt. OUT * on off * LED BO 74 98 2 Yes
6526 Inv. Undervoltage Up<-char.
picked up (Up< ch. pick.up)
Inv.Undervolt. OUT * on off * LED BO 74 99 2 Yes
6527 Inverse Undervoltage Up< TRIP
(Up< AUS)
Inv.Undervolt. OUT * on * LED BO 74 100 2 Yes
6530 Undervoltage protection switched
OFF (Undervolt. OFF)
Undervoltage OUT on
off
**LEDBO74301Yes
6531 Undervoltage protection is
BLOCKED (Undervolt. BLK)
Undervoltage OUT on
off
on off * LED BO 74 31 1 Yes
6532 Undervoltage protection is
ACTIVE (Undervolt. ACT)
Undervoltage OUT on
off
**LEDBO74321Yes
6533 Undervoltage U< picked up (U<
picked up)
Undervoltage OUT * on off * LED BO 74 33 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents