5-11
Pt. TYPE: SUPV Description: Supervisory Monitor (no alarm)
Circuit Status LCD Readout (2
nd
line) LED
Normal Supervision Monitor NORMAL
Limited Supervision Monitor SUPERVISORY S
Open Supervision Monitor TROUBLE T
Short Supervision Monitor SUPERVISORY S
Disable TBL Supervision Monitor TROUBLE T
Class A TBL Supervision Monitor TROUBLE T
Detailed Description: Used to monitor any supervisory type device where
operator acknowledgement is required.
Figure 5-29. SUPV Point Type
Pt. TYPE: UTIL Description: Utility Monitor with Tri-State (no
alarm)
Circuit Status LCD Readout (2
nd
line) LED
Normal Utility Monitor OFF
Limited Utility Monitor ON
Open Utility Monitor TROUBLE T
Short Utility Monitor ON
Disable TBL Utility Monitor TROUBLE T
Class A TBL Utility Monitor TROUBLE T
Detailed Description: Used to monitor and supervise any condition. Operator
acknowledgement is not required.
Figure 5-30. UTIL Point Type
Pt. TYPE: LATSUPV Description: Supervisory Latching
Circuit Status LCD Readout (2
nd
line) LED
Normal Supervisory Monitor NORMAL
Limited Supervisory Monitor SUPERVISORY S
Open Supervisory Monitor TROUBLE T
Short Supervisory Monitor SUPERVISORY S
Disable TBL Supervisory Monitor TROUBLE T
Class A TBL Supervisory Monitor TROUBLE T
Detailed Description: Used for generic supervisory alarm.
Figure 5-31. LATSUPV Point Type
Continued on next page
Point Type Messages for Monitor Points, Continued
Monitor Points (continued)
Technical Manuals Online! - http://www.tech-man.com