5-14
Pt. TYPE: CODED Description: Coded Signal
Circuit Status LCD Readout (2
nd
line) LED
Normal Coded Signal ON
Normal Coded Signal OFF
Normal Coded Signal CODING
Open Coded Signal TROUBLE T
Short Coded Signal TROUBLE T
Disable TBL Coded Signal TROUBLE T
Off Auto TBL Coded Signal TROUBLE T
Detailed Description: Used to indicate that the circuit will track a PNIS code.
NOTE: The 4005 does not support PNIS coding at this time.
Figure 5-36. CODED Point Type
Additional information about the circuit status can always be obtained. For
instance, a circuit that has the point type of CODED and has either a bad relay or
an open in the field wiring will display the screens shown in Figure 5-37.
Figure 5-37. Series of CODED Point information displays
Continued on next page
Point Type Messages for Signal Points, Continued
Signal Points (continued)
,2&DUG2XWSXW

&RGHG6LJQDO 7528%/( 
'HYLFH
6,*% &DUG
 3RLQW
&RGHG6LJQDO 2))
&RUUHFW'ULYH 5HOD\
2))
&ODVV$
1250$/
<ö> key
<ö> key
3K\VLFDO6WDWXV
23(1 (1$%/('
3ULRULW\
 $XWR&RQWURO
<ö> key
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4005 and is the answer not in the manual?

Simplex 4005 Specifications

General IconGeneral
BrandSimplex
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
CompatibilityCompatible with Simplex fire alarm control panels